12V load & battery sizing
Separate daily energy from simultaneous demand using your own equipment assumptions.
Use actual labels, manuals, and measurements. This worksheet does not certify equipment safety.
Collect the measurements first.
Blank fields have no assumed value. Enter zero for unused loads. The worked example below explains every input.
Start with appliances, not a battery size
A battery estimate begins with the work you want the system to do. List the appliances, their running power, and their equivalent full-power hours in a day. The worksheet provides three direct-current rows and three alternating-current rows. You can group additional appliances only when you preserve their total daily energy; keep a separate list so an omitted load does not disappear inside a convenient average.
The chemistry selector records which kind of battery you are considering. It does not choose a depth of discharge for you. Enter a usable fraction supported by the exact battery’s documentation and your chosen operating plan. Trojan’s battery guidance describes the relationship between discharge and life for its lead-acid products. Victron’s Lithium Smart technical data gives model-specific capacity and operating conditions. Neither establishes one setting for every battery of that chemistry.
Daily energy and nominal capacity
For each DC appliance, daily energy is watts multiplied by hours. For each AC appliance powered by an inverter, divide its watt-hours by the entered inverter efficiency as a decimal. Add the direct-current energy, adjusted AC energy, and the separate battery-side idle allowance. The result is estimated watt-hours drawn from the battery each day.
Divide daily watt-hours by nominal bank voltage to obtain estimated amp-hours per day. Multiply by the number of days without replenishment, then divide by the planned usable discharge fraction to obtain nominal bank capacity. The voltage must be appropriate to the selected battery. A nominal 12V system label does not mean every battery in that family has exactly 12.0V nominal voltage.
This is an energy-accounting model. It does not simulate changing terminal voltage, high-current capacity loss, cold conditions, aging, or battery-management cutoffs. There is no solar credit and no assumption that an alternator or shore charger will refill the bank during the entered autonomy period. If replenishment matters, document it separately and use a realistic measured energy balance.
Watts and watt-hours answer different questions
An appliance can use little daily energy but impose a large brief power demand. Enter the largest set of AC loads you intend to run simultaneously. That value cannot exceed the sum of the listed AC running watts and must include at least the largest active appliance. The worksheet adds your chosen percentage headroom to produce a running-power target.
Starting demand is reported separately as simultaneous running watts plus additional startup surge above that running value. Do not enter the full startup rating as an additional surge if it already includes running power. Check the duration for which an inverter can support its surge rating, the appliance’s actual startup needs, and any VA or power-factor specification. A watt total alone does not select a compatible inverter.
Check the example by hand
Use one DC load at an illustrative 40W for six equivalent full-power hours: 240Wh. Use one AC load at 100W for two hours: 200Wh at the appliance. At an assumed 90% inverter efficiency, the AC load takes about 222.22Wh from the battery. Add an illustrative 24Wh daily idle allowance and the daily battery-side estimate is 486.22Wh.
At a nominal 12.8V, that is about 37.99Ah per day. For two days without charging and an illustrative 80% usable discharge fraction, nominal capacity is approximately 94.97Ah, or 1,215.56Wh. These assumptions are demonstration inputs, not recommended settings for an unspecified battery. Enter zero watts and zero hours in the other appliance rows.
For the same example, enter a 100W simultaneous AC load, 25% chosen headroom, and zero additional surge. The running-power target is 125W and the starting-demand estimate is 100W. Those are distinct outputs; an actual purchase must satisfy the relevant continuous and transient requirements along with all other system constraints.
Use duty cycles deliberately
For a cycling refrigerator, equivalent full-power hours may be much less than elapsed hours. Alternatively, you can enter measured average power across the whole day and use 24 hours. Do one or the other, not both, or you may discount the consumption twice. When a manufacturer reports watt-hours per day, divide that energy by the chosen hours to create an equivalent row and retain the source conditions in your notes.
Idle consumption can also matter when an inverter stays on between appliance uses. Enter a measured or documented battery-side daily allowance. Do not assume a peak-efficiency figure from a specification sheet applies at every light load. Running a second scenario with less favorable efficiency is often more informative than adding unexplained extra capacity.
What remains outside the estimate
A qualified installer still needs to verify battery and BMS current limits, connections, protection, conductor sizing, ventilation, temperature restrictions, charging profiles, and equipment compatibility. This page does not provide wiring instructions or authorize a battery swap. Larger energy capacity does not automatically mean adequate peak-current capability.
Compare the worksheet with the actual installation and repeat it when appliance use changes. The battery load-audit guide explains how to keep an appliance ledger. The cooler-versus-fridge comparison shows why an appliance’s nameplate current and its daily energy use should not be treated as interchangeable.